Through automatic adjustment of the valve opening, it counteracts pressure fluctuations in the pipeline network to ensure stable supply and return water differential pressure in the controlled system, avoiding hydraulic imbalance caused by flow changes. It reduces energy waste caused by pressure fluctuations in the system, balances the hydraulic conditions of heating or air conditioning systems, and improves overall efficiency.
Application Scenarios
Other Fields
Some models can be extended to parallel systems of fire protection and domestic water, achieving flow control by adjusting the water supply direction.
Technical data
PN(MPa)Nominal pressure | 1.6 |
(MPa)Strength test | 2.4 |
(MPa)Seal test | 1.76 |
Working temperature | 0~100℃ |
Suitable mediums | Water |
Differential pressure control range |
10~30KPa |
Meterial of main parts
Part name | Meterial |
Body,bonnet | Cast iron,cast steel |
Stem | Stainless steel |
Diaphragm | NBR |
Valve disc | Cast steel |
Main dimensions
DN(mm) | L | H | Flow(m³h) | |
Constant pressure differential type |
Adjustable differential pressure type |
|||
15 | 110 | 95 | 145 | 0.2-1 |
20 | 110 | 110 | 150 | 0.3-1.5 |
25 | 115 | 130 | 165 | 0.5-2 |
32 | 130 | 140 | 190 | 1-4 |
40 | 200 | 190 | 340 | 1.5-6 |
50 | 215 | 205 | 355 | 2-8 |
65 | 230 | 240 | 390 | 3-12 |
80 | 275 | 300 | 500 | 5-20 |
100 | 290 | 350 | 550 | 10-30 |
125 | 310 | 380 | 580 | 15-45 |
150 | 350 | 410 | 410 | 30-75 |
200 | 430 | 480 | 480 | 40-180 |
250 | 520 | 100-300 | ||
300 | 630 | 150-1500 | ||
350 | 670 | 200-700 |